- Home
- Products
- ►
- Ballasts for fluorescent lamps
- ►
- Electronic dimming
- ►
- EXCEL compact series
PCA TC EXCEL one4all xitec II, 18 – 57 W
EXCEL compact
Product description
- Processor-controlled ballast with xitec II inside
- Highest possible energy class CELMA EEI = A1 BAT (1)
- Noise-free precise control via DALI or DSI signal, switchDIM or corridorFUNCTION
- Nominal lifetime up to 100,000 h (at ta 50 °C with a failure rate ≤ 0.2 % per 1,000 h)
- OEM-specific reserved memory areas
- Extended DALI commands
- 5 years guarantee
Interfaces
- DALI
- DSI
- switchDIM (with memory function + selectable dimming rate)
- corridorFUNCTION (3 preprogrammed profiles + individually programmable)
- Integrated SMART interface for function with all SMART Sensors and SMART plugs of the xitec II range
Functions
- Intelligent Temperature Guard (overtemperature protection)
- Intelligent Voltage Guard (overvoltage indication and undervoltage shutdown)
- Optimum filament heating in any dimmer setting
- Disconnection of filament heating from a dimming level of approx. 90 % for maximum energy efficiency (SMART-Heating concept)
- Fade rates between 100 ms and 90 s (min. – max.)
- corridorFUNCTION with ambient light control
- Automatically triggered emergency lighting value in DC mode 15 %, can be set between 3 and 100 %
- For emergency lighting systems as per EN 50172
- Automatic start after replacement of defective lamps
- Automatic shutdown if the lamp is faulty
- Dimming possible in DC mode
Ordering data | ||||
---|---|---|---|---|
Type | Article number | Packaging, carton | Packaging, pallet | Weight per pc. |
For luminaires with 1 lamp | ||||
PCA 1x26-57 TC EXCEL one4all xitec II | 22185128 | 10 pc(s). | 500 pc(s). | 0.163 kg |
PCA 1x55 T5c EXCEL one4all xitec II | 22185132 | 10 pc(s). | 500 pc(s). | 0.162 kg |
For luminaires with 2 lamps | ||||
PCA 2x26/32/42 TC EXCEL one4all xitec II | 22185129 | 10 pc(s). | 500 pc(s). | 0.206 kg |
- Lamp types:
-
-
-
- Approval marks:
-
-
-
-
-
-
-
Technical data | |
---|---|
Mains voltage range | 220 – 240 V |
AC voltage range | 198 – 264 V |
DC voltage range | 176 – 280 V (lamp start ≥ 198 V DC) |
Mains frequency | 0 / 50 / 60 Hz |
Overvoltage protection | 320 V AC, 1 h |
Typ. power input on stand-by | < 0.2 W |
Protective hot restart | 0.5 s for AC / 0.2 s for DC |
Dimming range | 3 – 100 % |
Lamp start possible from | 3 % |
Operating frequency | ~ 40 – 130 kHz |
Type of protection | IP20 |
Specific technical data | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Lamp wattage | Lamp type | Type | Article number | Dimensions L x W x H |
Lamp power (1) | Circuit power (1) | EEI | Current at 230 V, 50 Hz (1) | λ at 230 V, 50 Hz | tc point max. | Ambient temperature ta (2) |
For luminaires with 1 lamp | |||||||||||
1 x 40 W | T16-R (T5c) | PCA 1x26-57 TC EXCEL one4all xitec II | 22185128 | 123 x 79 x 31 mm | 40 W | 43.0 W | A1 BAT | 0.16 A | 0.97 | 75 °C | -25 ... +65 °C |
1 x 26 W | TC-DEL | PCA 1x26-57 TC EXCEL one4all xitec II | 22185128 | 123 x 79 x 31 mm | 24 W | 26.5 W | A1 BAT | 0.13 A | 0.95 | 75 °C | -25 ... +65 °C |
1 x 40 W | TC-L | PCA 1x26-57 TC EXCEL one4all xitec II | 22185128 | 123 x 79 x 31 mm | 40 W | 43.0 W | A1 BAT | 0.18 A | 0.97 | 75 °C | -25 ... +65 °C |
1 x 26 W | TC-TEL | PCA 1x26-57 TC EXCEL one4all xitec II | 22185128 | 123 x 79 x 31 mm | 24 W | 27.0 W | A1 BAT | 0.13 A | 0.95 | 75 °C | -25 ... +65 °C |
1 x 32 W | TC-TEL | PCA 1x26-57 TC EXCEL one4all xitec II | 22185128 | 123 x 79 x 31 mm | 32 W | 35.0 W | A1 BAT | 0.15 A | 0.96 | 75 °C | -25 ... +65 °C |
1 x 42 W | TC-TEL | PCA 1x26-57 TC EXCEL one4all xitec II | 22185128 | 123 x 79 x 31 mm | 42 W | 44.0 W | A1 BAT | 0.20 A | 0.98 | 75 °C | -25 ... +65 °C |
1 x 57 W | TC-TEL | PCA 1x26-57 TC EXCEL one4all xitec II | 22185128 | 123 x 79 x 31 mm | 57 W | 61.0 W | A1 BAT | 0.24 A | 0.98 | 75 °C | -25 ... +65 °C |
1 x 55 W | T16-R (T5c) | PCA 1x55 T5c EXCEL one4all xitec II | 22185132 | 123 x 79 x 31 mm | 55 W | 59.0 W | A1 BAT | 0.26 A | 0.98 | 70 °C | -25 ... +55 °C |
For luminaires with 2 lamps | |||||||||||
2 x 26 W | TC-DEL | PCA 2x26/32/42 TC EXCEL one4all xitec II | 22185129 | 123 x 102 x 31 mm | 48 W | 52.0 W | A1 BAT | 0.24 A | 0.96 | 75 °C | -25 ... +60 °C |
2 x 26 W | TC-TEL | PCA 2x26/32/42 TC EXCEL one4all xitec II | 22185129 | 123 x 102 x 31 mm | 48 W | 52.0 W | A1 BAT | 0.24 A | 0.96 | 75 °C | -25 ... +60 °C |
2 x 32 W | TC-TEL | PCA 2x26/32/42 TC EXCEL one4all xitec II | 22185129 | 123 x 102 x 31 mm | 64 W | 68.0 W | A1 BAT | 0.29 A | 0.97 | 75 °C | -25 ... +60 °C |
2 x 42 W | TC-TEL | PCA 2x26/32/42 TC EXCEL one4all xitec II | 22185129 | 123 x 102 x 31 mm | 84 W | 88.5 W | A1 BAT | 0.39 A | 0.98 | 75 °C | -25 ... +60 °C |
Further information
- FAQ – Digital dimmable ballasts (http://www.tridonic.com/com/en/faq-dimmable-ballasts.asp)
- Reference projects (http://www.tridonic.com/com/en/reference-projects.asp)
Software
Certificates / declarations of conformity | ||
Type | Article number | Certificates |
---|---|---|
Certificates () |