EM SELFTEST G2, 220 – 240 V 50/60 Hz

SELFTEST version

  • Note: Supply of control gear with duration link in 3 hours position. Remove duration link for duration of 1 h. Duration link must be set before battery and mains connection.

    Note: Supply of control gear with duration link in 3 hours position. Remove duration link for duration of 1 h. Duration link must be set before battery and mains connection.

Product description

  • Emergency lighting supply unit with selftest function
  • For linear and compact fluorescent lamps
  • Low profile casing (21 x 30 mm cross-section)
  • 5-year guarantee

Properties

  • Non maintained operation
  • Self-test as per IEC 62034
  • 1 or 3 h rated duration
  • Operating time selectable with plug (duration link)
  • Compatible with all electronic ballasts (dimmable and non-dimmable)
  • 5-pole technology: 4-pole lamp changeover and delayed power switching for the ballast
  • High-frequency ac operation of the lamp
  • Power control technology ensures maximum emergency ballast lumen factors (EBLF) for all lamps
  • Gentle on the lamp thanks to preheated lamp start and permanent cathode heating in emergency mode
  • 5.5 min. Boost start for rapid heating of the lamp, more light in the startup phase and optimum lamp life
  • Standard and high ballast lumen factor for 1-hour types
  • Electronic multi-level charge system
  • “Rest mode” function
  • Automatic commissioning
  • Automatic function and duration test at a time of low risk
  • Two-colour status display LED
  • Deep discharge protection
  • Very low energy consumption from the battery after activation of the deep discharge protection
  • Short-circuit-proof battery connection
  • Polarity reversal protection for battery
  • Self-test:
  • Status of the battery
  • Status of the lamp
  • Charge condition
  • Function test
  • Duration test

Batteries

  • High-temperature cells
  • NiCd or NiMH batteries
  • D, Cs or LA cells
  • 4-year design life
  • 1-year guarantee
Autoscroll for tables
Ordering data
Type Article number Battery type Number of cells Packaging, carton Packaging, pallet Weight per pc.
Rated operating time 1 h, High Output
EM 13 HO ST G2 89800229 NiCd 3 10 pc(s). 700 pc(s). 0.156 kg
EM 14 HO ST G2 89800232 NiCd 4 10 pc(s). 700 pc(s). 0.156 kg
EM 15 HO ST G2 89800235 NiCd 5 10 pc(s). 700 pc(s). 0.156 kg
EM 16 HO ST G2 89800238 NiCd 6 10 pc(s). 700 pc(s). 0.156 kg
EM 13 ST HO NiMh G2 89800340 NiMH 3 10 pc(s). 700 pc(s). 0.156 kg
EM 14 ST HO NiMh G2 89800341 NiMH 4 10 pc(s). 700 pc(s). 0.156 kg
EM 15 ST HO NiMh G2 89800342 NiMH 5 10 pc(s). 700 pc(s). 0.156 kg
EM 16 ST HO NiMh G2 89800343 NiMH 6 10 pc(s). 700 pc(s). 0.156 kg
Rated operating time 1 / 3 h, Standard BLF
EM 03 ST G2 89800198 NiCd 3 10 pc(s). 700 pc(s). 0.156 kg
EM 04 ST G2 89800201 NiCd 4 10 pc(s). 700 pc(s). 0.156 kg
EM 05 ST G2 89800204 NiCd 5 10 pc(s). 700 pc(s). 0.156 kg
EM 06 ST G2 89800207 NiCd 6 10 pc(s). 700 pc(s). 0.156 kg
EM 03 ST NiMh G2 89800336 NiMH 3 10 pc(s). 700 pc(s). 0.156 kg
EM 04 ST NiMh G2 89800337 NiMH 4 10 pc(s). 700 pc(s). 0.156 kg
EM 05 ST NiMh G2 89800338 NiMH 5 10 pc(s). 700 pc(s). 0.156 kg
EM 06 ST NiMh G2 89800339 NiMH 6 10 pc(s). 700 pc(s). 0.156 kg
Approval marks:
EAC
RCM
CE
ENEC
RoHs
Technical data
Rated supply voltage 220 – 240 V
Mains frequency 50 / 60 Hz
Mains current 60 mA
Rated power < 10 W
Overvoltage protection 320 V (for 1 h)
Maximum operating voltage (U-OUT of the ECG) 460 V
Battery charging time 1 h 10 h
Battery charging time 3 h 15 h
Discharge current, Standard BLF 1 A
Discharge current, High Output BLF 2.2 A
Time to light 1.2 s from detection of emergency event
Leakage current (PE) 0.5 mA
Ambient temperature ta -5 ... +60 °C
Max. casing temperature tc 70 °C
Mains voltage changeover threshold According to EN 60598-2-22
Min. lamp starting temperature (emergency mode) -5 °C
Type of protection IP20
Rest mode max. number of emergency units 100
Rest mode max. wiring distance 1,000 m
Autoscroll for tables
Specific technical data
Type Charge current / Battery charging time charge current / battery charge time
Initial charge / duration Fast re­charge / duration Trickle charge
Rated operating time 1 h, Standard BLF
EM 03 ST G2 130 mA / 20 h 210 mA / 10 h 50 mA
EM 04 ST G2 130 mA / 20 h 210 mA / 10 h 50 mA
EM 05 ST G2 130 mA / 20 h 210 mA / 10 h 50 mA
EM 06 ST G2 130 mA / 20 h 210 mA / 10 h 50 mA
EM 03 ST NiMh G2 130 mA / 20 h 210 mA / 10 h 130 mA / 4 min. – 0 mA / 16 min.
EM 04 ST NiMh G2 130 mA / 20 h 210 mA / 10 h 130 mA / 4 min. – 0 mA / 16 min.
EM 05 ST NiMh G2 130 mA / 20 h 210 mA / 10 h 130 mA / 4 min. – 0 mA / 16 min.
EM 06 ST NiMh G2 130 mA / 20 h 210 mA / 10 h 130 mA / 4 min. – 0 mA / 16 min.
Rated operating time 3 h, Standard BLF
EM 03 ST G2 300 mA / 20 h 330 mA / 15 h 130 mA
EM 04 ST G2 300 mA / 20 h 330 mA / 15 h 130 mA
EM 05 ST G2 300 mA / 20 h 330 mA / 15 h 130 mA
EM 06 ST G2 300 mA / 20 h 330 mA / 15 h 130 mA
EM 03 ST NiMh G2 300 mA / 20 h 330 mA / 15 h 200 mA / 4 min. – 0 mA / 16 min.
EM 04 ST NiMh G2 300 mA / 20 h 330 mA / 15 h 200 mA / 4 min. – 0 mA / 16 min.
EM 05 ST NiMh G2 300 mA / 20 h 330 mA / 15 h 200 mA / 4 min. – 0 mA / 16 min.
EM 06 ST NiMh G2 300 mA / 20 h 330 mA / 15 h 200 mA / 4 min. – 0 mA / 16 min.
Rated operating time 1h, High Output
EM 13 HO ST G2 300 mA / 20 h 330 mA / 15 h 130 mA
EM 14 HO ST G2 300 mA / 20 h 330 mA / 15 h 130 mA
EM 15 HO ST G2 300 mA / 20 h 330 mA / 15 h 130 mA
EM 16 HO ST G2 300 mA / 20 h 330 mA / 15 h 130 mA
EM 13 ST HO NiMh G2 300 mA / 20 h 330 mA / 15 h 200 mA / 4 min. – 0 mA / 16 min.
EM 14 ST HO NiMh G2 300 mA / 20 h 330 mA / 15 h 200 mA / 4 min. – 0 mA / 16 min.
EM 15 ST HO NiMh G2 300 mA / 20 h 330 mA / 15 h 200 mA / 4 min. – 0 mA / 16 min.
EM 16 ST HO NiMh G2 300 mA / 20 h 330 mA / 15 h 200 mA / 4 min. – 0 mA / 16 min.
Document      Size       Date       
Download all selected files Download all selected files
EM_SELFTEST_G2_220-240V_50-60Hz_en.pdf
Data sheet
1.66 MB 12/04/2016
Emergency_Lighting_Overview_EN.pdf
Emergency lighting
Solutions for emergency lighting
2.17 MB 03/10/2016
Certificates / declarations of conformity
Type      Article number      Certificates     
Certificates ()

Test switch EM3 Accessories

Approval marks:
RoHs

Product description

  • For connection to the emergency lighting unit
  • For checking the device function
  • Plug connection
Ordering data
Type Article number Packaging, bag Packaging, carton Weight per pc.
Test switch EM 3 89899956 25 pc(s). 200 pc(s). 0.01 kg

Status indication bi-colour LED EM CON Accessories

Product description

  • Two-colour status display LED
  • Green: system OK, red: fault
  • Plug connection
Ordering data
Type Type Article number Packaging, bag Packaging, carton Weight per pc.
LED EM bi-colour, 1.0 m CON 89800273 25 pc(s). 200 pc(s). 0.015 kg
LED EM bi-colour, high brightness HO 1.0 m CON 89800275 25 pc(s). 200 pc(s). 0.015 kg
LED EM 2-colour, 0.6 m CON 89800474 25 pc(s). 200 pc(s). 0.009 kg
LED EM 2-colour, high brightness HO 0.6 m CON 89800475 25 pc(s). 200 pc(s). 0.009 kg
LED EM bi-colour, 0.3 m CON 89800274 25 pc(s). 200 pc(s). 0.005 kg
LED EM bi-colour, high brightness HO 0.3 m CON 89800276 25 pc(s). 200 pc(s). 0.005 kg
Autoscroll for tables
CAD / RAY
Type Article number CAD Files
EM 13 HO ST G2 89800229 CAD (677.7 KB)
EM 14 HO ST G2 89800232 CAD (677.7 KB)
EM 15 HO ST G2 89800235 CAD (677.7 KB)
EM 16 HO ST G2 89800238 CAD (677.7 KB)
EM 13 ST HO NiMh G2 89800340 CAD (677.7 KB)
EM 14 ST HO NiMh G2 89800341 CAD (677.7 KB)
EM 15 ST HO NiMh G2 89800342 CAD (677.7 KB)
EM 16 ST HO NiMh G2 89800343 CAD (677.7 KB)
EM 03 ST G2 89800198 CAD (677.7 KB)
EM 04 ST G2 89800201 CAD (677.7 KB)
EM 05 ST G2 89800204 CAD (677.7 KB)
EM 06 ST G2 89800207 CAD (677.7 KB)
EM 03 ST NiMh G2 89800336 CAD (677.7 KB)
EM 04 ST NiMh G2 89800337 CAD (677.7 KB)
EM 05 ST NiMh G2 89800338 CAD (677.7 KB)
EM 06 ST NiMh G2 89800339 CAD (677.7 KB)

Please choose one of the following modules

Autoscroll for tables
Ordering data
Type Article number Configuration